Oil
Cooled Single Phase Potential Transformers
Construction
:
Outdoor oil cooled single phase
Potential Transformers are made for use on systems ranging
from 11kV to 33kV. The transformers are suitable for mounting
on structures, and basically consist of the following parts
:
a) Core
b) Winding
c) Insulation
d) Tank
e) Bushing
f) Oil Expansion Chamber
g) Secondary connection box
a)
The Core : The core is built from high grade transformer
steel sheet. Shell type construction of core is used in all
cases.
b)
The Winding : There are 2 main windings on every transformer.
The H.T. Winding and L.T. Winding. Special oil proof enamelled
Copper wire is used and wound in layers, each layer being
adequately insulated from the adjacent layers. Since the equipment
is for outdoor use, it is important that the windings are
designed suitably to withstand the surges to which the system
may be subjected. This is duly taken care of by proper grading
of the insulation in the various layers.
The L.T. winding is placed adjacent to the core and is insulated
from it for power frequency voltage test level of 2kV for
1 minute. Depending upon the requirement, two L.T. Windings
can be provided; one for metering and the other for protection.
In such case they are insulated from each other and also from
the core for power frequency voltage test level of 2kV for
1 minute.
c)
The Insulation : The insulation is in the form of oil
impregnated paper(Class A). The wound coils, duly insulated
with paper are thoroughly dried under vaccum before being
assembled. The oil used is high quality transformer oil which
is fully treated under vaccum before use.
d)
The Tank : The tank is made of sheet steel and is given
three coats of paint, both inside and outside, to avoid corrosion.
Suitable clamping arrangement is provided in the tank for
firmly bolting the core and the wound coils. The L.T. winding
terminals are brought out of the tank into secondary connection
box via suitable bakelite bushings. Two earthing studs, which
are welded to the tank are provided for earthing the transformer
whenthe connected into the system. The transformer is mounted
onto the structure by 4 nos. of suitable size of bolts and
nuts.
e)
The Bushing : The porcelain bushings used on the potential
transformers are as per BSS 223/1956 and suitable for use
in normally polluted atmosphere. The high voltage end/ends
of the H.T. winding, duly insulated are brought out of the
tank into the oil expansion chamber through bushings. The
bushings are mounted on the tank by suitable clamps. Neoprene
rubber gaskets are used to avoid any leakage of oil.
f)
The Oil Expansion Chamber : The oil expansion chamber
which is made of aluminium is fixed onto the bushing by using
epoxy resin. The high voltage end/ends of the H.T. winding
are connected to the oil expansion chamber. The volume of
the expansion chamber is designed to permit expansion of oil
due to the increase of ambient temperature. At the time of
despatch, the oil is filled only upto the top of the bushing
and there is no oil in the expansion chamber.
g)
The Secondary Connection Box : This box is welded on to
the transformer tank and is provided with a suitable cover
to protect the L.T. terminals from atmospheric hazards. A
suitable hole for entry of the L.T. cable is provided.
The
transformers are of fully sealed in construction and are supplied
filled with required quantity of oil. Provision of adequate
size oil expansion chamber does away with the need for a breather.
There
are 2 types of outdoor single phase Potential transformers.
These are :
1.) Suitable for connection between phase and nuetral
2.) Suitable for connection between phases
The
type designation used for outdoor oil cooled Potential Transformers
is VTO. This is followed by the rated voltage of the transformer
and the number after the oblique mark indicates whether the
transformer is of single bushing type or has both ends of
its H.T. winding insulated.
Maintenance
: No other maintenance apart from the occasional cleaning
of the insulator is considered necessary.
Technical
Informations Required for Tendering :
- Ratio
- Number of Secondary Windings
- 'VA' Burden of each windings
- Accuracy Class
- System Conditions;effectively or non-effectively earthed
- Voltage class
- Whether suitable for heavily or normally polluted atmosphere
conditions with creepage distance of insulator.
Standards
: IEC 60044-2;1997, IS 3156;1992
|